Home / Technical Library / ESFR, CMSA and CMDA storage sprinklers

ESFR, CMSA and CMDA storage sprinklers

Warehouse fires are hard to fight because the ceiling is high and the stored goods burn fast. NFPA 13 therefore has three main sprinkler approaches for storage: CMDA and CMSA aim to control the fire, while ESFR aims to suppress it.

The short answer

Side by side

CMDACMSAESFR
GoalControlControlSuppression
Design basisDensity/area curvesNFPA 13 decision tables; flow and pressure from several variablesNFPA 13 decision tables; flow and pressure from several variables
K-factorLarger than standard sprinklersK-11.2 minimumLarge K-factor, fast-response element
System typePer listingWet, dry or preaction, per listingWet systems only
Coverage per sprinklerPer NFPA 13 Chapters 20-2180 to 130 sq ft64 to 100 sq ft; spacing not over 12 ft
Typical design areaFrom the density/area curveRectangle; branch-line side at least 1.2 times the square root of the area12 hydraulically most demanding sprinklers (four on each of three lines)

CMDA: familiar, but built for storage

CMDA sprinklers look and spray much like standard commercial sprinklers. The difference is mainly a larger K-factor and higher temperature ratings. The required flow and pressure come from density/area curves, so the design method will feel familiar to anyone who has sized ordinary hazard systems.

CMSA: control with a larger orifice

CMSA sprinklers have large K-factors, at least K-11.2 for plume penetration, and a special deflector that produces different droplet sizes and spray patterns for high-challenge storage. They need a different listing from CMDA. Water demand depends on pile height, ceiling clearance, pile stability and storage array, and obstructions that disturb the discharge pattern should be avoided.

ESFR: suppression from the ceiling

ESFR sprinklers are used for high-piled storage of Class I-IV commodities, Group A plastics, rubber tires, rolled paper and similar. They are listed for wet systems only. Points that often decide a design:

What drives the choice

Selection depends on commodity class (I-IV plus plastics), storage arrangement (rack, solid-piled or palletized), ceiling height and whether goods are encapsulated in plastic, which raises water demand and limits stacking. Where ceiling-level protection is not enough, in-rack sprinklers are fitted inside the racks, usually with cage guards and water shields.

Check the building code too. Where the International Fire Code applies (high-piled storage above 12 feet, or 6 feet for high-hazard commodities) and conflicts with NFPA 13, the IFC governs.

Try it on your own layout

Our storage sprinkler selector checks Reliable and Tyco ESFR and standard sprinklers against your ceiling and storage height and calculates flow. For the full scope of work, see our fire protection services.

Sources

Summary for orientation only. Verify every value against the current edition of the standard and the manufacturer listing, and involve the authority having jurisdiction. This note does not replace a design by a qualified engineer.