FM-200, Novec 1230, inert gas or CO2: choosing the agent

Gas extinguishing protects rooms where water would do more harm than the fire: data centres, electrical and control rooms, archives, generator rooms. All four common choices work. The right one depends on who is in the room, how much space you have for cylinders, and what the project requires on environment and standards.

The short answer

Side by side

Novec 1230 FM-200 Inert gas CO2
Standard NFPA 2001, EN 15004 NFPA 2001, EN 15004 NFPA 2001, EN 15004 NFPA 12
How it works Absorbs heat Absorbs heat Lowers oxygen Lowers oxygen and cools
Storage Liquid, 25 / 42 / 50 bar Liquid, 25 / 42 bar Gas, 200 / 300 bar Liquid, high pressure
Cylinder space Low Low High Medium
Occupied rooms Yes, within standard limits Yes, within standard limits Yes, within standard limits No
Discharge time About 10 s About 10 s Within about 60 s Per NFPA 12
Ozone depletion 0 0 0 0
Global warming impact Very low High compared with the others None added Low per kg, but large quantities
Venting Normal Normal Pressure relief needed Lock-off and safe venting needed
Refill cost and supply Higher agent cost Moderate Low agent cost Lowest

How to decide

1. Will people be in the room? If yes, CO2 is out. The three other groups can be used in occupied rooms within the safety limits of the standard.

2. How much space can you give the cylinders? Clean chemical agents are stored as liquid and need few cylinders, close to the hazard. Inert gases are stored as compressed gas at 200 or 300 bar and need many more cylinders. In a tight building this alone often decides the choice.

3. What does the project require on environment? Inert gases and Novec 1230 have the lowest impact. FM-200 is a hydrofluorocarbon, and these are being phased down in some regions. For a new project, check what applies in your market and what your client or insurer accepts.

4. How big is the room, and how often will it discharge? Large rooms push the cylinder count up for inert gas. If you discharge often, agent refill cost matters.

5. Is the room tight enough? Every gas system holds its concentration for the hold time, usually 10 minutes. Leaks shorten it. Ask for a room integrity test before commissioning.

Detection and release matter as much as the agent

Gas is discharged only after detection confirms a fire, usually from two detectors in two zones (cross-zoned) to avoid false discharge. The release panel sounds a pre-discharge alarm and delay, ventilation is shut down and dampers close, then the cylinders open. After the hold time the room is ventilated safely before anyone enters.

Modular or engineered system

A modular (pre-engineered) system comes with cylinders, release panel, horn strobes, manual release, abort and detectors on a pre-built frame, and suits small and medium rooms. Larger or irregular spaces use engineered systems with a flow calculation for the pipework and nozzles.