LNG facilities handle cryogenic liquid and flammable vapour. Protection focuses on controlling spills and vapour, cooling equipment exposed to heat, and attacking fires with dry chemical and high-expansion foam.
Main fire risks
- Spills collecting in impounding areas and sumps
- Vapour clouds and jet fires
- Heat exposure to tanks, pipes and structures
- Loading and unloading at jetties and truck stations
How we protect it
- Foam extinguishing systems: High-expansion foam for impoundment areas
- Special extinguishing systems: Dry chemical systems for rapid flame knock-down
- Water extinguishing systems: Water spray for cooling exposed equipment and structures
- Fire pumps: Redundant diesel fire pump sets for the fire water system
- Fire detection and alarm systems: Gas, flame and low-temperature detection
Standards we design to
- NFPA 59A (LNG facilities)
- NFPA 11 (foam)
- NFPA 17 (dry chemical)
- NFPA 15 (water spray)
- NFPA 20 (fire pumps)
Our recommendations
- Do not use water on a cryogenic spill. Use it to cool exposed equipment, and use foam and dry chemical for the fire.
- Detect first and release second: gas and low-temperature detection should start the response before a fire starts.
- Design the fire water system to run on its own power, since the site may lose grid supply during an incident.