A sprinkler system finds a fire by heat and puts water on it at the spot where it started. It is the most widely used fixed fire protection in buildings because it needs no one to be present: the system works on its own, and only the sprinklers near the fire open.
The short answer
- Wet pipe: pipes are always full of water. Fastest and simplest. The first choice wherever there is no freezing risk.
- Dry pipe: pipes hold pressurised air or nitrogen. For unheated spaces such as cold stores, loading docks and some car parks. Water reaches the fire a little later.
- Preaction: water enters the pipes only when the detection system confirms a fire. For spaces where accidental discharge is unacceptable, such as archives and data rooms.
- Deluge: all sprinklers are open and discharge together when detection operates. For high-hazard areas where fire spreads fast, such as aircraft hangars and transformer areas.
How a sprinkler works
A sprinkler is held closed by a heat-sensitive glass bulb or a fusible link. When the temperature around that one sprinkler reaches its rating, the bulb breaks and water flows from that sprinkler only. It is a common misunderstanding that all sprinklers open at once in a fire. They do not, which is why sprinklers control a fire with limited water damage.
A complete system has a water supply (tank or mains), a fire pump and its controller where the supply pressure is not enough, a valve set with an alarm, the pipework and the sprinklers.
Choosing the system type
| Wet | Dry | Preaction | Deluge | |
|---|---|---|---|---|
| Pipe contents | Water | Air or nitrogen | Air or empty | Empty, open sprinklers |
| Water reaches fire | Immediately | After air is released | After detection and heat | Everywhere in the zone |
| Freezing risk | Not suitable | Suitable | Suitable | Suitable |
| Accidental discharge risk | Normal | Normal | Very low | Needs reliable detection |
| Typical use | Offices, hotels, retail, most warehouses | Cold stores, unheated areas | Archives, data rooms, museums | Hangars, process plants, transformers |
Dry, preaction and deluge systems cost more to build and need more care in maintenance. Choose them for the hazard, not by habit.
Design basis: hazard class decides the water
Sprinkler design starts from the hazard class of the space, because it sets how much water must be discharged and over what area.
- NFPA 13: Light Hazard, Ordinary Hazard (Group 1 and 2) and Extra Hazard (Group 1 and 2), plus separate rules for storage.
- EN 12845 (TS EN 12845): LH, OH, HHP and HHS classes.
The class gives a design density and design area, and the hydraulic calculation then finds the flow and pressure the system needs at the pump. Storage needs special attention: high racks and plastic goods can call for ESFR sprinklers or in-rack sprinklers. See ESFR, CMSA and CMDA storage sprinklers.
When are sprinklers required?
In Turkey the requirement comes from the Regulation on Fire Protection of Buildings (BYKHY). It sets the need for automatic fire suppression by building use, height, area and occupancy, so the answer depends on your building. Insurers and project specifications can also ask for sprinklers where the regulation does not. Confirm with the fire authority and your fire engineer early, as it changes the whole design.
What drives the cost
A price per square metre is misleading, because these items move the total most:
- Hazard class and design density, which set the water demand.
- Water tank volume and the fire pump set. The pump group, tank and controller are among the largest single items. See the fire pump selection guide.
- System type. Dry, preaction and deluge cost more than wet.
- Building geometry: ceiling height, obstructions, beams and rack layout.
- Sprinkler type: standard, ESFR, in-rack, concealed.
- Existing building work. Installing in a live building costs more than in a new one.
- Seismic bracing where it is required. See seismic bracing under NFPA 13.
A reliable budget needs a survey and a hydraulic calculation. Tekno Yangın can prepare both, and our Autosprink design service models the system in 3D.
After installation
A sprinkler system is only as good as its last inspection. Pumps, valves and alarms need regular tests, and the system needs inspection, testing and maintenance (ITM) to a recognised schedule. See our ITM service.
Sources
- NFPA 13, Standard for the Installation of Sprinkler Systems
- TS EN 12845, Fixed firefighting systems: Automatic sprinkler systems
- Regulation on Fire Protection of Buildings (BYKHY), mevzuat.gov.tr